Schneider Electric PCI-85.2:
Product Parameters:
- Model: PCI-85.2
- Type: Modbus Plus Interface Adapter
- Series: Modicon M580
- Bus Type: Modbus Plus
- Voltage: 3.3 or 5V per PCI (2.2) specification
- Current Consumption: 250 mA
- Physical and Electrical Characteristics: Shock (Non-operating 3 shocks/axis) 30g, 11ms, Free Fall (Unpackaged) 1 meter, Vibration Operating 10-57 Hz 0.07mmDA, 57-150 Hz 1g
- Dimensions: 10.67 cm x 16.76 cm (4.2 in. x 6.6 in.)
- Weight: 1 port 98 g (3.5 oz.), 2 port 102 g (3.6 oz.)
- Operating System: 32-bit drivers for Windows 98, Windows NT4.0 SP3 or higher, Windows 2000, and Windows XP (Home or Pro)
- Environmental: Storage Temperature -20 to 70 °C (Tested in accordance with IEC-60068-2-1 and IEC-60068-2-2.), Operating Temperature 0 °C to 55 °C, Relative humidity 10% to 90% RH, noncondensing
- Certifications: IEC 61010-1, EN 61010-1, UL 61010-1, CSA C22.2 No. 61010-1
Product Specifications:
- The PCI-85.2 is a Modbus Plus interface adapter that fits into a single PCI slot of an IBM PC or compatible computer. It allows computer-based applications to exchange data with Schneider Electric programmable logic controllers (PLCs) and other devices on the Modbus Plus network .
- It supports high-speed data transfer and ensures reliable communication between devices on the Modbus Plus network .
- The adapter is designed for use in various industrial automation applications where data exchange and communication are critical .
Features:
- Provides multi-voltage (3.3 and 5 volt) PCI bus plug and play support .
- Supports various programming software including Concept, Modsoft, ProWorx, and Unity .
- Compatible with a wide range of operating systems and industrial applications .
- Offers reliable performance in harsh industrial environments .
Application Fields:
- Industrial Automation: For use in machinery safety circuits to ensure safe operation of equipment .
- Building Automation: Integrating Modbus Plus devices into building management systems for efficient operation .
- Remote Monitoring: Enabling remote access to Modbus Plus devices for troubleshooting and maintenance .
- Any application requiring communication between PCI devices and Modbus Plus industrial networks